|

ESCSI
INFORMATION SHEET 3201 - NOVEMBER 1999
Energy Efficient
Buildings
with SmartWall Systems
When it comes to
energy performance SmartWall high performance concrete masonry systems
outperform metal stud walls with batt insulation and provide lower
heating and cooling cost. SmartWall Systems is helping to decrease
the overall global demand for energy.
SmartWall Systems
SmartWall is a high performance lightweight concrete masonry wall system
that outperforms other masonry and non-masonry wall systems, especially
in terms of energy efficiency, maintenance, appearance, fire resistance,
durability and strength to weight ratio. SmartWall is a mason friendly,
cost effective wall system that enhances speedy construction and has a
very high degree of customer satisfaction.
The SmartWall
System is Energy Efficient
SmartWall provides superior energy conservation by optimizing the combination
of R-values, thermal mass and low thermal bridging. Wall heating and cooling
costs may be reduced by more than 50%! The concrete in SmartWall has more
than 2.5 times the thermal resistance of the concrete in a typical heavy
block. This significantly reduces thermal bridging, maximizes the effectiveness
of core insulation, and results in the high R-value of SmartWall. As shown
in Table 1, an un-insulated SmartWall performs as well as core-insulated
heavy units! Also, SmartWall with perlite fill offers maximum thermal
performance.
In addition to thermal
resistance, SmartWall also benefits from thermal mass the flywheel
effect that minimizes peaks and valleys in heat load as a wall responds
to daily changes in ambient temperature. Walls with optimized thermal
mass reduce overall energy use, compared to non-masonry walls. SmartWall
has an ideal balance of thermal mass and thermal resistance for optimum
performance.
Calculating the overall
effect of thermal mass and thermal resistance in a walls dynamic
response to the environment is a complicated task. To perform this task,
the ASHRAE 90.1 energy code uses a computer program called ENVSTD, and
the results can be dramatic. For example, using ENVSTD to compare the
energy performance of a 12" SmartWall with perlite core insulation
to an R-19 batt insulated metal stud wall shows that SmartWall outperforms
the metal stud system! ENVSTD factors many variables besides opaque wall
properties, including glass area, shading, overhangs, and building orientation.
Using ENVSTD and SmartWall, energy efficient buildings can be designed
that comply with energy codes without the need for added-on insulation.
In many cases a single-wythe SmartWall does the job.
TABLE 1:
R-VALUES FOR CONCRETE MASONRY
WALLS (1) (Exposed Both Sides)
|
Nominal
Thickness
|
Concrete
Unit
Weight lbs/ft3
|
Cores
Empty
|
With
Core
Inserts
|
Cores
Filled
With Perlite
|
|
8"
|
SmartWall (2)
|
2.5
|
4.2
|
6.6
|
|
Heavy CMUs
(3)
|
1.9
|
2.6
|
3.2
|
|
12"
|
SmartWall (2)
|
2.7
|
4.4
|
9.5
|
|
Heavy CMUs
(2)
|
2.0
|
2.7
|
4.4
|
(1) R-Values
are mid-range per NCMA TEK 6.1A & 6.2A. R
in (háft2 áoF)BTU and includes 0.85 air film
coefficient. (2) SmartWall at 90 lbs/ft3. (3) Heavy CMUs
at 135 lbs/ft3.
ASHRAE Energy
Conservation Standard
The American Society of Heating, Refrigerating
and Air-Conditioning Engineers (ASHRAE) building energy conservation standard
clearly demonstrates that SmartWall Systems incorporating high performance
lightweight concrete masonry units are indeed energy efficient.
The Standard, ASHRAE/IES
90.1-1989 provides state of the art guidance regarding the design of energy
efficient buildings. Standard 90.1 recognizes the performance characteristics
of the materials used to construct the building rather than concentrating
on the R-values alone as earlier versions did. These characteristics include
the effects of wall thermal mass, thermal bridging and insulation position.
Thermal Mass -
Heat Capacity
The effects of wall thermal mass are well known. High thermal inertia
walls, such as stone, concrete masonry, SmartWall masonry, poured concrete
or clay brick, have the ability (due to their high heat capacity) to delay
and reduce the impact of outdoor temperature changes on conditioned indoor
environments. This means less heat gain or loss, depending on the season,
that must be supplied by energy consuming HVAC equipment. ASHRAE 90.1
quantifies thermal mass effects based on a walls heat capacity.
Heat capacity is defined as wall weight per square foot times specific
heat. Table 2 lists heat capacity for concrete masonry units, and Table
3 lists heat capacity for other common building materials.
Thermal Bridging
In buildings, when insulating material is interrupted by a highly conductive
material, thermal bridging takes place. Examples of thermal bridges include
steel studs that interrupt the continuity of batt insulation and metal
fasteners that go through heavily insulated exterior walls. Simply put,
thermal bridges occur where differences in material thermal conductivities
result in significant lateral heat flow; e.g., heat flowing along the
surface of a wall and then flowing through the wall via a steel stud.
ASHRAE 90.1 considers many thermal bridges. Table 4 (table 8C-2 in ASHRAE
90.1) lists the effect of thermal bridging in metal stud walls.
Example: The effects
of thermal bridging in a typical metal stud wall with 2x4 studs 16"
on center.
Uncorrected Insulation
R-value = R 11
Correction Factor = .5
Effective Insulation R-value = R 5.5
Table 2 lists concrete
masonry R-values calculated according to ASHRAEs series parallel
method recommended by the National Concrete Masonry Association. This
method accounts for thermal bridging within the CMU. Because of its low
thermal bridging characteristic, SmartWall Units with open cores (no insulation)
have the same R-values as heavy CMU with core insulation as shown in Table
1.
Calculating Thermal
Performance
ASHRAE 90.1 provides two methods for determining how the thermal properties
of walls impact building envelope energy-efficiency criteria. The first
method is prescriptive and provides 38 Alternate Component Package (ACP)
tables. The ACP tables list maximum wall Uo values, Uo = 1/R. The second
method is the systems performance method and it employs a computer based
program, Envelope Standard (ENVSTD). This approach requires input of many
building parameters including wall heat capacity and wall Uo. ENVSTD uses
these building-wide inputs to determine if the design meets the Standards
energy efficiency criteria. Because of this building-wide approach, SmartWall
CMU wall systems, with an optimized combination of heat capacity and R-values,
are found to be as energy efficient as "highly" insulated steel
stud wall systems. For ease of comparison, four energy compliance examples
are included on the following pages. The ENVSTD computer program was used
to verify the excellent energy performance of SmartWall high performance
concrete masonry walls. Each example uses the appropriate changes in the
Wall Uo, Heat Capacity values and INsulation POSition with all other building
parameters unchanged. Examples 1 & 2 compare an apartment building
in Milwaukee, Wisconsin. Examples 3 & 4 compare an office building
in El Paso, Texas. CONCLUSION.....For the examples considered, ENVSTD
proves that a 12" SmartWall System with perlite insulation uses less
energy for heating and cooling than a metal stud frame wall with R-19
batt insulation.
The Bottom Line
There are many ways to incorporate energy conservation into a building.
One of the most cost effective and environmentally friendly ways is to
consider the overall comfort of the users, as well as the total energy
consumption over the life of the structure. This not only helps the person
paying the heating and cooling bills, but also decreases the overall global
demand for energy benefitting both the user and the environment.
Thermal mass benefits
are not new. Throughout the ages, high mass building materials were the
product of choice for building strong, secure and comfortable structures
and dwellings. Its only in the past few decades we have become misdirected
with marketing emphasis only on the "R" value. Many have forgotten
that the truly comfortable buildings of the past had the energy conservation
built into the structural components. Now the ASHRAE 90.1 Standard provides
the needed link between energy theory and the real world.
By designing buildings
with the high performing SmartWall Systems, owners will get energy conservation
built into the structure without complicated and expensive add-ons to
insulate the building envelope. SmartWall masonry units are made with
expanded shale, clay or slate (ESCS) aggregate. They are mason friendly
and up to 40% lighter than obsolete heavy masonry units. Additionally,
SmartWall offers superior fire resistance, sound absorption, reduced seismic
loading and low shrinkage.
As a building owner
or designer you can choose a system with a practical "R" number
that when combined with thermal inertia, obtains proven energy performance
with quiet comfort. The SmartWall system maximizes all the benefits of
traditional masonry: design flexibility, economy, thermal mass and durability.
In addition, the lighter weight SmartWall system benefits the mason because
of fewer injuries, safer scaffolds, longer working career and the opportunity
for female workers. Since increased productivity is a natural consequence
of lighter units, overall construction time is often reduced. SmartWall
meets the needs of todays market, and gives specifiers all the best
reasons to choose concrete masonry. SmartWall is the Answer!
(The following
tables and examples are in
format.)
TABLE
2: THERMAL PROPERTIES
OF CONCRETE MASONRY WALLS
TABLE
3: THERMAL PROPERTIES
OF VARIOUS BUILDING MATERIALS
TABLE
4: (ASHRAE 90.1 Table 8C-2)Wall Sections
with Metal Studs Parallel Path Correction Factors
EXAMPLES
1 & 2 - Apartment in Milwaukee, WI
12" SmartWall Systems Wall compared with typical face brick steel
stud wall
EXAMPLE
3 & 4- Office Building in El Paso, TX
12" SmartWall Systems Wall compared with typical face brick steel
stud wall
For additional
information please contact ESCSI
via Phone: (801) 272-7070, Fax: (801) 272-3377,
e-mail: info@escsi.org or visit ESCSIs web site
at www.smartwall.org.
ESCSI
INFORMATION SHEET 3201 - NOVEMBER 1999

|